Q4. Lamp should glow after a delay of 25 sec when start switch S1 is made ON and should remain ON in glowing condition even the switch is made OFF.Lamp should go OFF immediately when a reset switch S2 is made ON.


fig. Q4.


  • In first rung of the program,reset NC contact is connected in series with parallel connected start and B3 NO contact and then B3 output coil.
  • so in first rung when we press the start button the B3 coil gets activated and just because of the B3 NO contact connected in parallel with start button so B3 output coil gets in continuous ON state.
  • In second rung of program NO B3 contact is connected to TON timer with preset value 25 sec, so when the start button is pressed timer gets ON immediately.
  • In third rung of program NO contact with done bit address of timer is connected to lamp,so the lamp gets ON after 25 sec if the start button is pressed and reset button is OFF.
  • In middle of the 25 sec if reset button is pressed timer gets reset and output will not gets ON.
 

Comments

Popular posts from this blog

HOW TO DOWNLOAD AND INSTALL WONDERWARE FOR WINDOWS 8,7,10.

##You can Download a ZIP file of the software From Below link. https://drive.google.com/file/d/159y8W0c_bw0vvf1DNDQ08_QsLZ9h2Tb1/view?usp=sharing 1 ) You Can Also Watch a Video Tutorial of it  below. 2) You can also read out steps from below :-

Bit Logic Instruction in Simatic manager

There are total 14 instructions under the bit logic instruction like NO contact, NC contact, SR flip-flop, RS flip-flop,invert power flow etc. lets see the detailed use of them.  A) Normally open contact :- Normally open contacts are closed when the bit value stored at the specific address is equal to 1 (one)(here the specific address refers to the address assigned to the NO contact), when we press the Normally open contact assigned to the specific address then it becomes functionally closed and we get supply. here in below fig. when we press the NO contact I0.0 then Output Q0.0 gets ON and when we release the input I0.0 then Output gets OFF. B)Normally Closed Contact :- Normally closed contacts are closed when the bit value stored at the specific add, i.e. the address assigned to the NC contact is equal to 0(zero). when we press the Normally closed contact assigned to the specific address then it becomes functionally open and supply is cuts off. NC contact wor...

Timer instruction

In mitsubishi PLC Gx-Developer programming software we have total 512 timers From T0 - T511. These timers are categorized into 5 groups depending upon the time base and type of timer as :- T0 - T199 timers works as Done bit of TON timer (time base-100ms). T200 - T245 timers works as Done bit of TON timer (time base-10 ms). T246 - T249 timers works as Done bit of retentive timer (time base- 1 ms). T250 - T255 timers works as Done bit of retentive timer (time base-100 ms). T256 - T511 timers works as Done bit of TON timer (time base- 1 ms). You may be aware of the working of the TON timer and RTO timer, which works similarly of TON and Retentive timers in AB PLC, the only difference is you only get the done bit of timers in mitsubishi PLC. To enter proper preset value to the timers of various time bases we need to convert the seconds into the respective time bases. Below table shows the conversion of pre-set values into the respective time bases. We can use the sa...