Skip to main content

When Start PB is pressed, The Output energizes. When PB is released, the output still remains ON till stop button is pressed.



sol:-

   
 









       here i have given two solution for same the problem statement.
      first solution is of two rungs and second solution is one rung solution both gives the same results.

 (in first solution):- when start press button is pressed the latch coil gets activated and remain active even if the start press button is released so the output remains on and when the stop button is pressed it will unlatch the same coil and thus the output goes off or reset.

(in the second solution):-  when the press button is pressed then it will activate the output and one NO contact is placed in parallel with the start NO contact so as soon as the output coil gets activated it will close the NO contact in parallel with the start button and it will maintain the connection and when the stop NC button is pressed it will disconnect the supply and it will reset the output to zero.

Comments

Popular posts from this blog

Timers in Siemens PLC Simatic manager

Timer :- Timer is nothing but a specialized clock in a programming software used to count the preset time intervals. In   Siemens PLC we have various ty pes of timers as :- 1) S_PULSE(Pulse timer), 2) S_PEXT(Extended Pulse Timer), 3) S_ODT(On Delay Timer), 4) S_ODTS(Retentive On Delay Timer), 5) S_OFFDT(Off Delay Timer). You must find out another five instruction sets in Timer Block in Simatic Manager STEP 7 as :- -(SP) pulse timer coil, -(SE) extended pulse timer coil, -(SD) on delay timer coil, -(SS) retentive on delay timer coil, -(SF) off delay timer coil. 1) S_PULSE(Pulse timer) :- S_PULSE Timer   Above Fig Shows how to use this timer in programming software,in this fig i have used 5 sec as a preset value, If you want to change it replace the 5 with any duration you want in S5T# 5 S.    In S_PULSE timer if input to timer is ON then timer starts Counting time as well as we get the Output at the instant the input is made ON. In t...

HOW TO DOWNLOAD AND INSTALL WONDERWARE FOR WINDOWS 8,7,10.

##You can Download a ZIP file of the software From Below link. https://drive.google.com/file/d/159y8W0c_bw0vvf1DNDQ08_QsLZ9h2Tb1/view?usp=sharing 1 ) You Can Also Watch a Video Tutorial of it  below. 2) You can also read out steps from below :-

Bit Logic Instruction in Simatic manager

There are total 14 instructions under the bit logic instruction like NO contact, NC contact, SR flip-flop, RS flip-flop,invert power flow etc. lets see the detailed use of them.  A) Normally open contact :- Normally open contacts are closed when the bit value stored at the specific address is equal to 1 (one)(here the specific address refers to the address assigned to the NO contact), when we press the Normally open contact assigned to the specific address then it becomes functionally closed and we get supply. here in below fig. when we press the NO contact I0.0 then Output Q0.0 gets ON and when we release the input I0.0 then Output gets OFF. B)Normally Closed Contact :- Normally closed contacts are closed when the bit value stored at the specific add, i.e. the address assigned to the NC contact is equal to 0(zero). when we press the Normally closed contact assigned to the specific address then it becomes functionally open and supply is cuts off. NC contact wor...